Mineral insulated cables
Mineral Insulated Heating Cable,single core up to 480 °C
Application:
Moisture proof applications at high outputs and temperatures
High-temperature sistuations
Can be immersed in fluids
Chemical & petrochemical industries
Machinery and plant construction
Molten Salt Applications
Vacuum technology
Heat tracing on piping
Heat tracing on vessels
Standard:
EN 60079-30-1
Voltage Rating:
500V
CABLE CONSTRUCTION:
Conductors: Solid alloy or copper conductor.
Insulation: Magnesium Oxide (MgO).
Outer sheath: Stainless Steel 1.4541 (AISI 321).
Mechanical and Thermal Properties:
Maximum Operating temperature: 480℃
Maximum continuous exposure temperature: 600℃
Minimum installation temperature: -60℃
Bending radius: 6×OD
Nominal output: 250 W/m
Cold lead, length: 2 x 0.50 m
Cold lead, cross section: 2.50 mm²
Impact resistance: 7 J
Cable Parameter:
Overall Diameter mm | Resistance at 20 °C ohms/km |
Temperature coefficient x 10¯³/K |
---|---|---|
3.20 |
10000 |
0.09 |
3.20 |
6300 |
0.09 |
3.20 |
4000 |
0.09 |
3.40 |
2500 |
0.09 |
3.60 |
1600 |
0.09 |
3.90 |
1000 |
0.09 |
4.30 |
630 |
0.09 |
4.70 |
400 |
0.09 |
5.30 |
250 |
0.09 |
6.50 |
160 |
0.09 |